E1FU | Ex eb, Ex db, Ex nR, Ex ta | Explosive Atmosphere Cable Gland

For all types of Armoured cables

Description

Globally Approved, Explosive Atmosphere Cable Gland

• Metal-to-metal armour clamping
• Direct & remote installation
• Displacement type flameproof inner seal
• Controlled outer ‘load retention’ seal
• Unique OSTG prevents overtightening
• Designed to prevent Coldflow, see CMP Technical Document TS001 (available upon request)
• -60°C to +130°C
• Globally marked, IECEx, ATEX & cCSAus
• Superior EMC performance

Note: † Grooved Cone (X) is predominantly used for Wire Braid (e.g. GSWB, TCWB), Steel Tape Armour (STA, DSTA) and Aluminium Strip Armour (ASA) but is also suitable for Single Wire Armour (SWA), Aluminium Wire Armour (AWA) and Pliable Wire Armour (PWA) if the range is outside that of the Stepped Cone (W). Note: Grooved Cone (X) dimensions shown in the Cable Gland Selection Table below are for a double wire strand of braid armour cables. Tapes can also be doubled over. For cables that have only a single layer of armour such as SWA the clamping range should be used as shown in the table below. Stepped (W) Cone is suitable for Single Wire Armour (SWA), or Aluminium Wire Armour (AWA) cables. For under

Technical Data

Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444
Mechanical Classifications * Impact = Level 8, Retention = Class D
Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only
Electrical Classifications * Category B (Category A when used with braid, tape or pliable wire armour cables)
ATEX Certificate CML 18ATEX1324XCML 18ATEX4316X
UKEX Certificate CML 21UKEX1252X,CML 21UKEX4253X
Code of Protection  II 2G, II 1D, Ex db IIC Gb, Ex eb IIC Gb, Ex ta IIIC Da
II 3G Ex nR IIC Gc,  IM2 Ex db I Mb, Ex eb I Mb
Compliance Standards EN 60079-0,1,7,15,31
IECEx Certificate IECEx CML 18.0181X
Code of Protection Ex db IIC Gb, Ex eb IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da, Ex db I Mb, Ex eb I Mb
Compliance Standards IEC 60079-0,1,7,15,31
cCSAus Certificate (20s16 – 90) 1310517
CSAus Code of Protection Class II, Div 2, Groups E,F and G, Class III, Enclosure Type 4X,
Class I, Zone 1, AEx e II, AEx nR II
cCSA Code of Protection Class I, Div 2, Groups A,B,C and D, Class II, Div 2, Groups E,F and G, Class III, Enclosure Type 4X,
Ex d IIC, Ex e II, Ex nR II
Code of Protection Ex d IIC; Ex e II; Ex nR II; Class I, Div 2, Groups A,B,C,D, Class II, Div 2 Groups E,F,G, Class III;
Encl Type T4X Class I, Zone 1, AEx e II / AEx nR II
Compliance Standards CAN/CSA-C22.2 No 0,18,25,30,174,94, CAN/CSA-E60079-0,1,7,15
ANSI/UL 514B Ed 5, ANSI/UL 50 Ed 11, ANSI/UL 2225 Ed 4, UL60079-0,1,7,15
EAC Certificate C-GB.A07.B.02515/20
KCs Certificate 14-GA4BO-0257X
CCC Certificate 2020322313002870
CCOE / PESO (India) Certificate Ex d: P548696Ex e: P533772 Ex nR: P548695
INMETRO Approval TÜV 12.0618X
RETIE Approval 03866
UkrSEPRO CU 19.0371X
SANS MS-XPL21804 21.0010X
Marine Approvals LRS: 01/00173DNV: TAE00000YABS: 20-LD1948801-PDABV: 43180/A1BV
Ingress Protection Rating ** IP66 as standard (IP67, IP68 available upon request)
Deluge Protection Compliance DTS01:91 option available on request (white ferrule for identification purposes)
Cable Gland Material Brass, Electroless Nickel Plated Brass, Aluminium
Seal Material CMP SOLO LSF Halogen Free Thermoset Elastomer
Cable Type Single Wire Armour (SWA), Aluminium Wire Armour (AWA), Steel Tape Armour (STA), Wire
Braid Armour (e.g. SWB), Aluminium Strip Armour (ASA), Pliable Wire Armour (PWA),
Screened Flexible (EMC) Wire Braid (e.g. CY / SY), Armoured & Jacketed
Armour Clamping Reversible Armour Cone & AnyWay Universal Clamping Ring
Sealing Technique CMP Inner Displacement Seal & Unique CMP ‘LRS’ ™ Outer Load Retention Seal
Sealing Area(s) Cable Inner Bedding & Outer Cable Sheath
Optional Accessories LocknutsEarth TagsSerrated WashersEntry Thread SealsShrouds,Ingress Discs
Optional Installation Tools SpannersArmour Former Tool
ECAS Certificate 24-03-106290/E24-03-110155/NB0007

Note : * Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444
** When CMP installation accessories are used. Refer to Maintaining a Seal for further information.
*** IP68 tested to a minimum depth of 30 metres for 12 hours, alternate depths / durations can be provided upon request